We're one of the most professional FA One-stop suppliers in China.Our main products including servo motor, planetary gearbox, inverter and PLC, HMI.Brands including Panasonic, Mitsubishi, Yaskawa, Delta, TECO, Sanyo Denki ,Scheider, Siemens , Omron and etc.; Shipping time: Within 3-5 working days after getting the payment. Payment way: T/T, L/C, PayPal, West Union, Alipay, Wechat and so on
The EL9410 power supply terminal is used to refresh the E-bus. Data is exchanged between the coupler and the EtherCAT Terminal over the E-bus. Each terminal draws a certain amount of current from the E-bus (see “current consumption E-bus” in the technical data). This current is fed into the E-bus by the relevant coupler’s power supply unit. In configurations with a large number of terminals it is possible to use the EL9410 in order to supply an extra 2 A to the E-bus. In addition to the E-bus refresh, a 24 V DC supply of up to 10 A can be provided for the power contacts. The EL9410 has a diagnostic function which is displayed by LED and on the process image.
| Technical data | EL9410 |
|---|---|
| Technology | power supply terminal |
| Short-circuit proof | yes |
| Input voltage | 24 V DC (-15%/+20%) |
| Input current | typ. 70 mA + (E-bus/4) |
| Output voltage | 5 V for E-bus supply |
| Output current | 2 A |
| Current consumption E-bus | – |
| Electrical isolation | 500 V (E-bus/field potential) |
| Power contacts | max. 24 V DC/max. 10 A |
| Diagnostics in the process image | yes |
| Special features | standard EL supply |
| Weight | approx. 65 g |
| Operating/storage temperature | 0…+55°C/-25…+85°C |
| Relative humidity | 95%, no condensation |
| EMC immunity/emission | conforms to EN 61000-6-2/EN 61000-6-4 |
| Vibration/shock resistance | conforms to EN 60068-2-6/EN 60068-2-27 |
| Pluggable wiring | for all ESxxxx terminals |
| Protect. rating/installation pos. | IP20/variable |
| Approvals/markings | CE, UL, ATEX, IECEx |
| Ex marking | ATEX: II 3 G Ex ec IIC T4 Gc IECEx: Ex ec IIC T4 Gc |